Obvius / Leviton AcquiSuite – EMB A8810
AcquiSuite – EMB A8810
Energy Monitoring Hub EMB ModBus/TCP/Ethernet. Power Supply Not Included.
The compact AcquiSuite – EMB footprint and industrial temperature range (-30 to 70C) makes this a perfect solution for embedded applications. Reduce development time and speed up integration by collecting and distributing energy information directly from your equipment.
Data Collection
The AcquiSuite – EMB collects and logs data from connected (wired or wireless) devices based on user selected intervals. Data from downstream devices is time stamped and stored locally in non-volatile memory until the next scheduled upload or manual download. Using an Ethernet (LAN) connection you can push or pull data via HTTP, XML, FTP or any custom protocol utilizing our AcquiSuite Module to build your own application.
Installation & Features
No software is required – easily access information through ANY web browser. There are several additional features including alarming, SNMP Traps, network configuration, wireless diagnostics, USB, security provisions and backlit LCD. Our integrated meter driver library is designed to speed up installation and lower integration costs through “plug-and-play” connectivity.
Compatibility
The AcquiSuite A8810 is compatible with nearly any front-end software platform allowing customers to use a variety of reporting tools; whether it’s a local server or an enterprise wide reporting suite.
The EMB A8810 is also an accepted data integration logger to be used with the Panoramic Power Front End. Its data logging, storage and data upload capabilities provides a simple path to integrate I/O data. The data is stored locally on the EMB A8810 and is uploaded to the Panoramic Power server for dashboarding. Data uploads can range from 1 minute to every 24 hours.
Key Features
No software is required - easily access information through ANY web browser. There are several additional features including alarming, SNMP Traps, network configuration, wireless diagnostics, USB, security provisions and backlit LCD. Our integrated meter driver library is designed to speed up installation and lower integration costs through "plug-and-play" connectivity.
Application
- Push or pull meter data to energy dashboards, kiosks and software applications
- Meet performance-based incentives
- Measurement and verification (M&V)
- Reduce energy costs
- Access energy information from local or remote sites
- Benchmark building energy usage
- View “real time” performance data
- Track energy use and peak demand for Demand Response programs
- Monitor performance of critical systems (lighting, HVAC, PDUs, inverters, etc.)
- Alarm notification for data points above or below target levels (including SNMP Traps)
- Monitor renewable energy performance and production
- LEED / Energy Star certification
Upgrade to v02.16.0916 is Available
- Virtual Metering: This new functionality allows users to create virtual meters and calculated data points
- Selective Data Uploading: Identify which data you want uploaded for each upload destination
- Remote Assistance: With the assistance of an Obvius technical service rep, and remote connection can now be easily created via the touch of AcquiSuite's onboard buttons
- Backup and Restore: Users may now copy all AcquiSuite's setting and backup for future usage and deployment allowing for better protection in case of data loss while saving on installation time
- Extended Memory: Increase the AcquiSuite's logged data stortage capacity
Specifications
Processor | ARM9 embedded CPU |
Operating System | Linux 2.6 |
Memory | 32 MB RAM |
Flash ROM | 16 MB NOR Flash (expandable with USB memory device) |
Interval Recording | 1 to 60 minutes, user selectable (default 15 minutes) |
LEDs | Ethernet, Modbus TX/RX, power, alarm |
Console | 2 x 16 LCD character, two push buttons |
Power | |
---|---|
Power Supply | 24VDC, 500mA |
* This unit is to be sourced by a Class 2 power supply with the following output: 24VDC, 500mA min not to exceed 8A | |
Isolation | RJ45 Ethernet and RS-485 port are isolated to 1500VDC from the main board. (Power and USB non-isolated) |
Communication | |
Protocols | Modbus/RTU, Modbus/TCP, TCP/IP, PPP, HTTP/HTML, FTP, NTP, XML, SNMP-Trap |
LAN | RJ45 10/100 Ethernet, full half duplex, auto polarity |
USB | USB expansion port |
Inputs | |
Serial | Port RS-485 Modbus, supports up to 32 external devices (expandable) |
Physical | |
Weight | 0.42lbs (0.19kg) |
Size | 4" x 4.25" x 2" (102mm x 108mm x 51mm) |
Environment | |
North America | -30 to 70C, 95% RH, non-condensing |
Codes and Standards | |
FCC CFR 47 Part 15, Class A, EN 61000, EN 61326, CE, UL61010 Recognized | |
Additional Notes | |
NEMA enclosures available upon request | |
Cellular modems available upon request | |
Manufactured in the USA |